Viledon High Efficiency Extended Surface Filters - 12" MV Series, MVFR, CarboPleat, DuoPleat
  MV75 MV85 MV95 MV95FR CarboPleat DuoPleat
Rated Air Flow (cfm) 2000 2000 2000 2000 2000 2000
Average Dust Spot Efficiency (%)* 80 85 96 96 N/A 95
Initial Efficiency on Particles >1 micron  (%) >69 >71 >93.5 >93.5 N/A >91
Initial Resistance(in. w.g.) 0.24 0.27 0.30 0.30 0.30 0.44
Max.Temperature(ºF) 160,
peaks 175
160,
peaks 175
160,
peaks 175
160,
peaks 175
160 160
UL 900 Classification Class 2 Class 2 Class 2 Class 1 - -
Depth(in) 11.5 11.5 11.5 11.5 11.5 11.5
Size Availability 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2

* According to ASHRAE 52.1 - 1992

For more information, call us at 1-888-924-6233.