Viledon High Efficiency Filters for Gas Turbine - 12" MV Series and Depth-loading Filter Cartridges TFP 60 & TFP 90

Progressive media structure 500pm

Intake air filtration for a gas turbine with TFP 60
  MV75 MV85 MV95
Rated Air Flow (cfm) 2000 2000 2000
Average Dust Spot Efficiency (%)* 75 85 95
Initial Efficiency on Particles >1 micron(%) >80 >91 >94
Initial Resistance (in. w.g.) 0.27 0.29 0.33
Max. Temperature (ºF) 160,
peaks 175
160,
peaks 175
160,
peaks 175
UL 900 Classification Class 2 Class 2 Class 2
Depth (in) 11.5 11.5 11.5
Size Availability 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2

 

* According to ASHRAE 52.1 - 1992

Depth-loading Filter Cartridges TFP 60 and TFP 90

  Unit TFP60 TFP90
Filtering area ft2(m2) 33 (3) 120 (11)
Thermal stability °F (ºC) 158°F (70°C)
Peaks to 176°F (80°C)
158°F (70°C)
Peaks to 176°F (80°C)
Moisture resistance % 100 100
Average arrestance % 99 100
Average efficiency % 65 96
Nominal volume flow rate ft3/m (m3/h) 600 (1000) 600 (1000)
Initial pressure drop in. H2O (Pa) 0.44 (108) 0.44 (109)
Recommended final pressure drop in. H2O (Pa) 3.2 (800) 3.2 (800)
Dust holding capacity*
(ISO Fine / 3.2 in. H2O, 800 Pa)
oz (g) 81 (2300) 42 (1200)

 

* According to ASHRAE 52.1 - 1992

For more information, call us at 1-888-924-6233.

print close